德州紫旭空调设备有限公司为您提供消防前室压力传感器布线-紫旭空调-前室压力传感器。压力传感器前室压力传感器
加压后的风再分别通过每层的百叶窗或风阀送往每层的前室或楼梯间。当消防前室或楼梯间的通风压力或压差超过设定值前室25~30pa,楼梯间40-50pa时,位于每层的压力传感器顺即时发出信号报警输入旁通泄压阀控制箱,消防前室压力传感器布线,旁通泄压阀控制箱根据压力传感器的信号打开旁通泄压阀,旁通泄压阀打开后,部分加压送风机送往风管的风通过旁路风管经过旁通泄压阀回到风机前端红色箭头位置
the compressed air is then sent to the front room/stairwell of each floor through the shutters/the air valve. when the ventilation pressure/pressure difference in the fire chamber/stairwell exceeds the set value (25 ~ 30 pa in the front chamber&40-50 pa in the stairwell) , the pressure sensor located on each floor immediately sends a signal to the by-pass pressure relief valve control box,前室压力传感器, the by-pass pressure relief valve control box opens the by-pass pressure relief valve according to the signal of the pressure sensor, part of the pressurized air supply fan to the air duct through the bypass air duct by-pass relief valve back to the fan front (red arrow ition)
余压探测器前室压力传感器
德州紫旭豪鲁邦消防应急疏散余压控制器消防应急疏散余压控制器
cr-yykz消防应急疏散余压控制器
1、完全满足《建筑防排烟系统技术规范》;
2、可监控疏散通道上余压、以pid控制方式控制泄压阀,调节余压在安全范围内;
3、向监控主机反馈现场工作状态,合用前室压力传感器,联动余压传感器调节泄压阀;
4、现场就地取消防电源作为工作电源,合用前室压力传感器作用,可以灵活构建大容量余压监控系统;
5、每个回路可带载128只余压传感器;
6、可以持续调节泄压阀的开启角度。
于压差传感器,在我们甲方群里有几点疑问:
1、 这个压差传感是给消防做还是弱电做?
2、 压差传感如何安装?
就这两个问题,以下做一个系统的总结和交流。
一、划在哪个标段?
压力传感器控制系统其实是一套独立的联动系统,可以是弱电做也可以是消防来做,但是后都要消防来调试并负责验收,所以个人建议为避免扯皮,还是放在消防标段比较合适。
二、如何安装?
要谈如何安装,先介绍一下系统:
这个系统主要为控制柜、线路和末端传感器三个部分。
消防前室压力传感器布线-紫旭空调-前室压力传感器由德州紫旭空调设备有限公司提供。消防前室压力传感器布线-紫旭空调-前室压力传感器是德州紫旭空调设备有限公司今年新升级推出的,以上图片仅供参考,请您拨打本页面或图片上的联系电话,索取联系人:危经理。