消防前室压力传感器批发常用解决方案 紫旭空调没有中间商
前室压力控制器
电梯前室通常要求其空间内部气压高于外部气压 10~15pa ;而高层建筑前室(包括消防电梯前室、楼梯间前室、合用前室、三合一前室、共用前室等)要求是25~30pa,楼梯间要求是 40~50pa
通常要求其空间内部气压高于外部气压 10~15pa ;而高层建筑前室(包括消防电梯前室、楼梯间前室、合用前室、三合一前室、共用前室等)要求是25~30pa,楼梯间要求是 40~50pa
前室压力探测器消防前室压力传感器批发
when the supply air volume&time of itive pressure air supply system is out of control, the normal escape route may be too high because of the itive pressure of the front room, the fire door can not open the serious cequences. in view of the above ciderati, the sichuan institute of fire science combined with experience to provide data of residual pressure value. by controlling the opening&closing of the by-pass valve, the differential control system can effectively control the residual pressure of the mechanical pressurized air supply system within the reasonable range required by the national standard ——40-50 pa in the smoke-proof stairwell, the front room, the shared front room, the front room of the fire elevator room&the enclosed refuge floor (room) are 25-30pa.
压力传感器控制箱消防前室压力传感器批发
通用型压差控制器广泛应用于前室合用前室压差测控系统、封闭避难层、防烟楼梯间压差测控系统;室内外压差检测、过滤网堵塞监控系统等干燥气体的压差测控系统。
特点:
◆带一个绿色巡检指示灯,一个红色报警指示灯;◆直接输出开关控制信号;◆供电及信号输出采用总线制传输;
产品参数:
量 程:0~100pa 控制器寿命: 10万次
耐 压:1000pa 电气等级: 24 vdc/0.3a
动作压力: 切 换 率: 大6次/分钟
前室/走道:25~30pa,(复位压力:15~20pa); 外形尺寸:172*112*60